First Letter Succeeding Letters Measured or Initiating Variable Modifier Readout or Passive Function Output Function Modifier A Analysis Alarm B Burner, Combustion User’s Choice User’s Choice User’s Choice C User’s Choice Control D User’s Choice Differential E Voltage Sensory (Primary) F Flow Rate Ratio (fraction) G User’s Choice Glass, Viewing H Hand High I Current Indicate J Power Scan K Time,
Time ScheduleTime Rate of Change Control Station L Level Light Low M User’s Choice Momentary Middle N User’s Choice User’s Choice User’s Choice User’s Choice O User’s Choice Orifice P Pressure, Vacuum Point, Test Q Quantity Integrate, Totalize R Radiation Record S Speed, Frequency Safety Switch T Temperature Transmit U Multivariable Multifunction Multifunction Multifunction V Vibration W Weight, Force Well X Unclassified x-axis Unclassified Unclassified Unclassified Y Event, State y-axis Relay, Compute Z Position, Dimension z-axis Driver, Actuator
(Adapted from Bruce G. Lovelace, "Piping and Instrument Diagrams", handout given at seminar held at Michigan Technological University, Dept. of Chemical Engineering, November 5, 1992)